Tutorial

MicroLogix 1400 Modbus RTU Control of Delta VFD-M

Allen-Bradley MicroLogix Modbus Control of Delta VFD-M

7 min read

Industry

Industrial Automation

Category

VFD & Drives

Type

Tutorial

Read Time

7 min read

MicroLogix 1400 “Modbus RTU” Control of Delta VFD-M

Introduction

The Delta VFD-M series, though discontinued and replaced by newer models like the MS300, remains a prevalent choice in industrial machinery. Due to its widespread use, there are still many instances where engineers and technicians need to interface with this older inverter model. This guide will walk you through the process of using a MicroLogix 1400 PLC to control a Delta VFD-M inverter via Modbus-RTU (RS485) communication.

This tutorial provides detailed instructions on wiring, parameter configuration, and programming to ensure a seamless and efficient setup.

1. MicroLogix 1400 & Delta VFD-M Wiring Diagram

To begin, you need to establish the correct wiring connections between the MicroLogix 1400 PLC and the Delta VFD-M inverter. The preferred method is using the 1763-NC01 module for easy wiring; however, direct connections to the RS485 port of the MicroLogix 1400 PLC (Mini DIN – 8 Pin) are also possible.

MicroLogix 1400 & Delta VFD-M Wiring Diagram

Wiring Tips:

2. Delta VFD-M Parameter Configuration

For successful communication and control of the Delta VFD-M via Modbus-RTU, certain parameters need to be configured on the inverter. These configurations align the VFD’s communication settings with those of the MicroLogix 1400 PLC.

Essential Parameter Configurations:

  1. Pr00: = 03 (Frequency Setting via RS485)
  2. Pr01: = 04 (Motor Control via RS485)
  3. Pr88: = 01 (Modbus Slave Address)
  4. Pr89: = 01 (Baud Rate: 9600bps)
  5. Pr92: = 04 (Modbus RTU Configuration: 8-bit, 1 stop bit, Even parity)
  6. Pr157: = 01 (Modbus RTU Selection)

These parameters ensure that the Delta VFD-M is properly set up to receive and respond to commands from the MicroLogix 1400 PLC via Modbus-RTU.

3. Delta VFD-M Registers Address for Control

Controlling the Delta VFD-M involves writing specific values to its Modbus registers. Here, we will cover the main register addresses used for motor control and frequency setting.

Motor Control Register Address:

Frequency Setting Register Address:

Delta VFD-M Control Register Table

These register addresses and corresponding values allow you to control the basic operations of the VFD, such as starting, stopping, and adjusting the motor speed.

4. Delta VFD-M Registers Address for Monitoring

Monitoring the Delta VFD-M’s performance involves reading specific output registers. These registers provide real-time data on various operational parameters, including frequency, current, and voltage.

Monitoring Register Addresses:

Faizal Afzal recommends reading five output registers to monitor:

  1. Frequency Command
  2. Output Frequency
  3. Output Current
  4. DC-BUS Voltage
  5. Output Voltage

Delta VFD-M Monitoring Register Table

These monitoring addresses are essential for tracking the VFD’s operational status and ensuring it functions correctly within the desired parameters.

5. MicroLogix 1400 Modbus RTU Configuration

To establish communication between the MicroLogix 1400 PLC and the Delta VFD-M, you need to configure Channel 0 on the PLC for RS485 communication. The settings must match the communication parameters set on the VFD.

Channel 0 (RS485) Configuration Steps:

  1. Set the communication protocol to Modbus RTU.
  2. Match the Baud Rate with the VFD (9600bps).
  3. Configure Data Bits to 8, Stop Bit to 1, and Parity to Even.
  4. Assign the correct Node Address that corresponds with the VFD.

MicroLogix 1400 RS485 Configuration Screen

Proper configuration ensures that the MicroLogix 1400 PLC can successfully communicate with and control the Delta VFD-M.

6. MicroLogix 1400 PLC Programming

Finally, you will need to program the MicroLogix 1400 PLC to handle both the control and monitoring tasks for the Delta VFD-M. Below are the critical programming components required for effective VFD management.

Programming Components:


These programming steps integrate the control and monitoring of the Delta VFD-M into your automation system, providing seamless operation and feedback.

Conclusion

This professional guide provides a comprehensive approach to controlling the Delta VFD-M using a MicroLogix 1400 PLC via Modbus-RTU communication. From wiring and parameter configuration to PLC programming, each step is designed to ensure that you can efficiently and effectively manage the VFD within your industrial processes.

By following this guide, you will be able to maintain and control older Delta VFD-M inverters, ensuring continued reliability and performance in your operations.

Recent Work

Asset Tracking & Monitoring
Smart Utility Management Solution
Mobility Solutions for Industry 4.0
Overall Equipment Effectiveness (OEE)
Predictive Maintenance Solution
Enhancing Alarm Management Efficiency
OT/SCADA Data Backup Management
Condition Based Maintenance (CbM)
Centralized Backup for SCADA/OT
Strengthening Security in SCADA/ICS
Zero Trust Security Approach
3-Step Strategy for Cyber Resilience